PR Electronics 2 Channel Galvanic Barrier, Pulse, ATEX
- RS Stock No.:
- 136-8697
- Mfr. Part No.:
- 5202B1
- Manufacturer:
- PR Electronics
Subtotal (1 unit)*
PHP17,522.02
(exc. VAT)
PHP19,624.66
(inc. VAT)
FREE delivery for orders over ₱3,000.00
In Stock
- Plus 1 unit(s) shipping from April 27, 2026
- Plus 3 unit(s) shipping from May 04, 2026
Need more? Click ‘Check delivery dates’ to find extra stock and lead times.
Units | Per Unit |
|---|---|
| 1 + | PHP17,522.02 |
*price indicative
- RS Stock No.:
- 136-8697
- Mfr. Part No.:
- 5202B1
- Manufacturer:
- PR Electronics
Specifications
Technical data sheets
Legislation and Compliance
Product Details
Find similar products by selecting one or more attributes.
Select all | Attribute | Value |
|---|---|---|
| Brand | PR Electronics | |
| Number of Channels | 2 | |
| Product Type | Galvanic Barrier | |
| Barrier Type | Galvanic Barrier | |
| Mount Type | DIN Rail | |
| Hazardous Area Certification | ATEX | |
| Terminal Type | Screw | |
| IP Rating | IP20 | |
| Signal Type | Pulse | |
| Maximum Safety Current | 400mA | |
| Maximum Safety Voltage | 300V dc | |
| Minimum Operating Temperature | -20°C | |
| Maximum Operating Temperature | 60°C | |
| Standards/Approvals | 2014/35/EU, ATEX 2014/34/EU, EN 60947-5-6, EAC Ex TR-CU 012/2011, IEC 61140, 2014/30/EU, UL 508 | |
| Series | 5200 | |
| Select all | ||
|---|---|---|
Brand PR Electronics | ||
Number of Channels 2 | ||
Product Type Galvanic Barrier | ||
Barrier Type Galvanic Barrier | ||
Mount Type DIN Rail | ||
Hazardous Area Certification ATEX | ||
Terminal Type Screw | ||
IP Rating IP20 | ||
Signal Type Pulse | ||
Maximum Safety Current 400mA | ||
Maximum Safety Voltage 300V dc | ||
Minimum Operating Temperature -20°C | ||
Maximum Operating Temperature 60°C | ||
Standards/Approvals 2014/35/EU, ATEX 2014/34/EU, EN 60947-5-6, EAC Ex TR-CU 012/2011, IEC 61140, 2014/30/EU, UL 508 | ||
Series 5200 | ||
- COO (Country of Origin):
- DK
PR Electronics 5202B Ex Pulse Isolator
PR Electronics 5202B pulse isolator for transmission of signals to the safe area from NAMUR sensors installed in hazardous areas. This signal conditioning isolator measures one or more pulse inputs and provides an identical number of isolated pulse outputs. The PR 5202B uses transformer and optical isolation techniques to provide 3.75 kVac galvanic isolation between the input, output and power terminals. The high level of electrical isolation means that input pulses sensed at the 5202B are not electrically connected to the output pulse. The 5202B has been designed, developed and certified for use in SIL 2 applications according to the requirements of IEC 61508.
Besides providing isolation, the PR 5202B is a barrier. This means that the module can make an intrinsically safe measurement of contacts and NAMUR sensors mounted in a zone 0/ Division 1 explosion hazard area. The PR 5202B limits the level of energy present at the contact or the NAMUR sensor to a low intrinsically safe level, thereby preventing ignition of a flammable atmosphere around the sensor – even if the sensor or the cable is damaged.
Features and Benefits
• 3.75 kVac galvanic isolation between input, output and supply
• One input signal can be used on two separate outputs
• A cable error alarm can be detected on a separate output
• Designed, developed and certified for use in SIL 2 applications
• Front LED indicates operation status and malfunction
• DIN rail mounting