PR Electronics 1 Channel Galvanic Barrier, ATEX, IECEx
- RS Stock No.:
- 136-8691
- Mfr. Part No.:
- 5106BBA
- Manufacturer:
- PR Electronics
Currently unavailable
We don't know if this item will be back in stock, RS intend to remove it from our range soon.
- RS Stock No.:
- 136-8691
- Mfr. Part No.:
- 5106BBA
- Manufacturer:
- PR Electronics
Specifications
Technical data sheets
Legislation and Compliance
Product Details
Find similar products by selecting one or more attributes.
Select all | Attribute | Value |
|---|---|---|
| Brand | PR Electronics | |
| Number of Channels | 1 | |
| Product Type | Galvanic Barrier | |
| Barrier Type | Galvanic Barrier | |
| Mount Type | DIN Rail | |
| Hazardous Area Certification | ATEX, IECEx | |
| Safety Current Resistance | 10Ω | |
| Terminal Type | Screw | |
| IP Rating | IP20 | |
| Maximum Safety Voltage | 300V dc | |
| Maximum Safety Current | 400mA | |
| Minimum Operating Temperature | -20°C | |
| Maximum Operating Temperature | 60°C | |
| Standards/Approvals | EAC, CE, DNV GL, UL | |
| Series | 5100 | |
| Select all | ||
|---|---|---|
Brand PR Electronics | ||
Number of Channels 1 | ||
Product Type Galvanic Barrier | ||
Barrier Type Galvanic Barrier | ||
Mount Type DIN Rail | ||
Hazardous Area Certification ATEX, IECEx | ||
Safety Current Resistance 10Ω | ||
Terminal Type Screw | ||
IP Rating IP20 | ||
Maximum Safety Voltage 300V dc | ||
Maximum Safety Current 400mA | ||
Minimum Operating Temperature -20°C | ||
Maximum Operating Temperature 60°C | ||
Standards/Approvals EAC, CE, DNV GL, UL | ||
Series 5100 | ||
5106B I.S. HART Transparent Repeater
PR Electronics 5106B intrinsically safe HART transparent repeater is a signal isolator with 2-way HART communication for 2-wire transmitters installed in the hazardous area. The 5106B signal conditioner is based on microprocessor technology for gain and offset. The analogue signal is transmitted at a response time of less than 25 ms. Mounted vertically or horizontally on a DIN rail. As the devices can be mounted without distance between neighbouring units, up to 84 channels can be mounted per meter..
Features and Benefits
• 3.75 kV ac galvanic isolation
• Inputs, outputs and supply are floating and galvanically separated
• Output can be connected either as an active current transmitter or as a 2-wire transmitter
• Low response time
• Universal supply by AC or DC
•DIN Rail mounting (vertically or horizontally)
What is HART Protocol?
The HART protocol is a low speed, digital communications scheme that is carried on a 4 to 20 mA current signal. As 4 to 20 mA loops are commonly used in industry, the HART protocol is easy to implement, easy to use, and easy to troubleshoot. Devices that communicate via HART are popular in many industries.