- RS Stock No.:
- 414-673
- Mfr. Part No.:
- TIA32M50
- Manufacturer:
- Eaton
100 In PH stock for Delivery NCR Plus within 2 working days, rest of PH within 7 working days
15 In Global stock for delivery. NCR Plus within 10 working day(s), rest of PH within 14 working days
65 In Global stock for delivery. NCR Plus within 10 working day(s), rest of PH within 14 working days
Added
Price Each (In a Pack of 5)
PHP1,136.638
(exc. VAT)
PHP1,273.035
(inc. VAT)
Units | Per Unit | Per Pack* |
5 - 120 | PHP1,136.638 | PHP5,683.19 |
125 - 495 | PHP1,112.772 | PHP5,563.86 |
500 + | PHP1,079.39 | PHP5,396.95 |
*price indicative |
- RS Stock No.:
- 414-673
- Mfr. Part No.:
- TIA32M50
- Manufacturer:
- Eaton
Technical data sheets
Legislation and Compliance
RoHS Status: Not Applicable
Product Details
Red Spot™ Range, Type T HBC
As the fuse allows for the starting surge of a motor its full load current must not exceed the lesser of the dual current rating. e.g. 20 M25 must not have a continuous load of greater than 20A
Features and Benefits
Breaking capacity 80kA ac 40kAdc
Rated up to 550Vac/ 250Vdc (Type A1) & 660Vac/ 460Vdc (Type A2)
General purpose (gG) and dual motor rated (gM) types
Low power dissipation
660Vac rated (A1 types 415Vac)
ASTA 20 certified
Rated up to 550Vac/ 250Vdc (Type A1) & 660Vac/ 460Vdc (Type A2)
General purpose (gG) and dual motor rated (gM) types
Low power dissipation
660Vac rated (A1 types 415Vac)
ASTA 20 certified
As the fuse allows for the starting surge of a motor its full load current must not exceed the lesser of the dual current rating. e.g. 20 M25 must not have a continuous load of greater than 20A.
Eaton British Standard Fuse, A2, 32A TIA32M50
This high-performance fuse from the Eaton range is specifically designed for the protection of motor circuits. It's a slow-acting fuse that allows temporary inrush currents to pass without breaking the flow. It only breaks the flow when a surge or overload is sustained. This makes it useful for motors that need short bursts of current at startup.
The bolted tags are 8.7mm wide and attach easily to fuse holders for improved electrical safety. This component is commonly found in packaging and processing plants where motors are used in the various stages of production.
The bolted tags are 8.7mm wide and attach easily to fuse holders for improved electrical safety. This component is commonly found in packaging and processing plants where motors are used in the various stages of production.
Features & Benefits
Low power dissipation for improved energy efficiency
Length of 85.5mm for standard installation
High breaking capacity of 80kA to prevent fires from electrical arcing
Low temperature rise for high-density mounting
32A current rating makes it suitable for heavy-duty applications
Length of 85.5mm for standard installation
High breaking capacity of 80kA to prevent fires from electrical arcing
Low temperature rise for high-density mounting
32A current rating makes it suitable for heavy-duty applications
Can I use a fuse with an AC rating in a DC system?
A fuse with an AC (alternating current) rating should not be used in a DC (direct current) system. However, there are fuses that have both V AC and V DC ratings and can be used in both systems.
Note
Eaton formerly known as Bussmann
Specifications
Attribute | Value |
---|---|
Current Rating | 32A |
Fuse Size | A2 |
Voltage Rating | 660V ac |
Fuse Standard | BS 88-2, IEC 269-2 |
Fixing Centres | 73mm |
Application Category | gG, gM |
Tag Width | 8.7mm |
Fuse Speed | T |
High Rupture Capacity | Yes |
Overall Length | 85.5mm |
Tag Type | Bolted |
Body Diameter | 22.2mm |
Tag Orientation | Offset |
Body Height | 56.4mm |
Fuse Dimensions | 22 x 86mm |
Series | Bussmann |