Specifications
Technical data sheets
Legislation and Compliance
Product Details
Find similar products by selecting one or more attributes.
Select all | Attribute | Value |
|---|---|---|
| Brand | Siemens | |
| Product Type | Monitoring Relay | |
| Electrical Phase | 3 | |
| Contact Configuration | DPDT | |
| Mount Type | DIN Rail | |
| Terminal Type | Screw | |
| Time Delay | 0.1 to 30 s | |
| IP Rating | IP20 | |
| Minimum Operating Temperature | -25°C | |
| Maximum Operating Temperature | 60°C | |
| Height | 100mm | |
| Length | 90mm | |
| Series | 3UG5 | |
| Standards/Approvals | UL, IEC 60664, RoHS, EAC, CCC | |
| Better World Product | Yes | |
| Better World Claim | Concentrated or Compact Solution | |
| Select all | ||
|---|---|---|
Brand Siemens | ||
Product Type Monitoring Relay | ||
Electrical Phase 3 | ||
Contact Configuration DPDT | ||
Mount Type DIN Rail | ||
Terminal Type Screw | ||
Time Delay 0.1 to 30 s | ||
IP Rating IP20 | ||
Minimum Operating Temperature -25°C | ||
Maximum Operating Temperature 60°C | ||
Height 100mm | ||
Length 90mm | ||
Series 3UG5 | ||
Standards/Approvals UL, IEC 60664, RoHS, EAC, CCC | ||
Better World Product Yes | ||
Better World Claim Concentrated or Compact Solution | ||
- COO (Country of Origin):
- DE
Siemens 3UG5 Series Monitoring Relay, 120 to 400V Supply AC Voltage, 0.1 to 30s Time Delay - 3UG5616-1CR20
This monitoring relay is a digitally adjustable network monitor designed for line supervision in three-phase AC installations. It checks phase sequence, phase loss, asymmetry, frequency and both over- and undervoltage within industrial supply networks, and provides relay switching to protect downstream equipment in control panels mounted on a 35mm DIN rail.
Features & Benefits
• 0.1–30 s adjustable response delay for tailored start-up protection
• Monitors 3 x 90–690 V AC and 15–70 Hz for wide voltage/frequency ranges
• Two changeover contacts delivering 3A switching for control circuits
• Auto-reset and adjustable N-conductor recognition for flexible operation
• Detects phase asymmetry and phase failure to prevent motor stress
• Screw terminals accepting up to 4 mm² conductors for secure connections
• Monitors 3 x 90–690 V AC and 15–70 Hz for wide voltage/frequency ranges
• Two changeover contacts delivering 3A switching for control circuits
• Auto-reset and adjustable N-conductor recognition for flexible operation
• Detects phase asymmetry and phase failure to prevent motor stress
• Screw terminals accepting up to 4 mm² conductors for secure connections
Applications
• Suitable for monitoring supply integrity to three-phase motors
• Ideal for integration into machine control panels on DIN rails
• Used for protective supervision of distribution boards and feeders
• Can be used for frequency-sensitive equipment protection
• Suitable for installations requiring adjustable voltage window detection
• Ideal for integration into machine control panels on DIN rails
• Used for protective supervision of distribution boards and feeders
• Can be used for frequency-sensitive equipment protection
• Suitable for installations requiring adjustable voltage window detection
What input supply voltages will operate the device?
It accepts AC control supply from 120–690 V across 50/60 Hz with an operating range factor from 0.85 to 1.1.
How precise is the voltage and timing measurement?
Relative metering precision is 3% with a digital-display accuracy of ±1 digit and temperature drift of 0.001%/°C.
What isolation and surge resilience does it provide?
The unit offers galvanic isolation between inputs and outputs and surge resistance up to 6kV, with conductor-to-conductor surge rating to 1kV.
What are the expected mechanical and electrical lifetimes?
Typical mechanical life is 10 million cycles and electrical endurance around 100,000 cycles at AC-15/230 V.
How should short-circuit protection be arranged for the relay contacts?
Use gL/gG fuses rated 6 A or an MCB type C at 1 A for protecting both NO and NC contact circuits.
Related links
- Siemens Monitoring Relay DPDT 120/690 V ac
- Siemens Monitoring Relay DPDT 690 V ac 690 V dc
- Siemens Monitoring Relay 3 Phase DIN Rail 90/400 V ac
- Siemens Monitoring Relay DPDT 200/690 V ac
- Siemens Monitoring Relay DPDT 690 V dc
- Siemens Monitoring Relay 90/760 V ac Monitor Range DIN Rail, 690 V ac
- Siemens Monitoring Relay DPDT 500 V ac
- Siemens Monitoring Relay DPDT 43A to 10mA, 24/240 V ac