Specifications
Technical data sheets
Legislation and Compliance
Product Details
Find similar products by selecting one or more attributes.
Select all | Attribute | Value |
|---|---|---|
| Brand | Phoenix Contact | |
| Number of Channels | 2 | |
| Product Type | Galvanic Barrier | |
| Barrier Type | Galvanic Barrier | |
| Mount Type | DIN Rail | |
| Hazardous Area Certification | ATEX | |
| Safety Current Resistance | 450Ω | |
| Terminal Type | Screw | |
| IP Rating | IP20 | |
| Maximum Safety Voltage | 125, 253V dc | |
| Signal Type | Analogue | |
| Minimum Operating Temperature | -20°C | |
| Maximum Safety Current | 20mA | |
| Maximum Operating Temperature | 60°C | |
| Standards/Approvals | CE, IEC, WEEE, RoHS, ATEX, UL | |
| Series | MACX MCR-EX-SL-2RPSSI | |
| Select all | ||
|---|---|---|
Brand Phoenix Contact | ||
Number of Channels 2 | ||
Product Type Galvanic Barrier | ||
Barrier Type Galvanic Barrier | ||
Mount Type DIN Rail | ||
Hazardous Area Certification ATEX | ||
Safety Current Resistance 450Ω | ||
Terminal Type Screw | ||
IP Rating IP20 | ||
Maximum Safety Voltage 125, 253V dc | ||
Signal Type Analogue | ||
Minimum Operating Temperature -20°C | ||
Maximum Safety Current 20mA | ||
Maximum Operating Temperature 60°C | ||
Standards/Approvals CE, IEC, WEEE, RoHS, ATEX, UL | ||
Series MACX MCR-EX-SL-2RPSSI | ||
- COO (Country of Origin):
- DE
Phoenix Contact Galvanic Barrier, 20mA, 2 Channels - MACX MCR-EX-SL-RPSS-2I-2I - 2865382
This Phoenix Contact galvanic barrier isolates the signal to your power supply and converts it for measurement. The device is designed for use in explosive environments, enabling safe data collection. It has a wide operating temperature range of -20°C to +60°C, so it's safe to use in harsh conditions.
The status of the supply voltage is conveniently displayed by the green LED (light-emitting diode) light, so you can check it's wired up correctly and works effectively with the circuit. This device is compatible with HART (highway addressable remote transducer) devices, meaning it can transmit signals across analogue wires from a field sensor to a control system. It's commonly connected to a PLC (programmable logic controller) to produce readable results.
Features & Benefits
• Typical transmission error of less than 0.05% of final value for a high degree of accuracy
• Polyamide (PA) housing material has high tensile and compressive strength for long-lasting use
• IP20 (ingress protection) rating means it's touchproof for enhanced safety
• Minimal power dissipation of
MACX MCR-SL-RPSSI-I Series Repeater Power Supply / Signal Conditioner
The intrinsically safe interface blocks of the MACX Analog Ex series offer the widest range of functions in the narrowest design.
Ex-i signal conditioner for many applications
Electrical 3-way isolation
Screw or spring-cage connections are available
IP20 protection
Width only 12.5 mm
Approvals
CE