GEORGIN 1 Channel Double Zener Barrier, ATEX

Subtotal (1 box of 1 unit)*

PHP11,037.48

(exc. VAT)

PHP12,361.98

(inc. VAT)

Add to Basket
Select or type quantity
Stock information currently inaccessible - Please check back later
Box(es)
Per Box
1 +PHP11,037.48

*price indicative

RS Stock No.:
230-9461
Mfr. Part No.:
BZG788PLUS
Manufacturer:
GEORGIN
Find similar products by selecting one or more attributes.
Select all

Brand

GEORGIN

Number of Channels

1

Product Type

Double Zener Barrier

Barrier Type

Zener Barrier

Mount Type

DIN Rail

Hazardous Area Certification

ATEX

Terminal Type

Screw

IP Rating

IP20

Minimum Operating Temperature

-20°C

Maximum Safety Voltage

28V

Maximum Safety Current

245.11mA

Maximum Operating Temperature

60°C

Standards/Approvals

IECEx IEC 60079-0/IEC 60079-11/IEC 60079-15/IEC 61241-11/IEC 61241-0, D.B.T. NFC 15-100, ATEX EN 60079-0/EN 60079-11/EN 60079-15/EN 61241-11/EN 61241-0, C.E.M. EN 61326-1 & IEC61000-6-2, SIL EN 61508 (SIL 2 or SIL 3)

Series

BZG

Zener barriers contribute to the intrinsic safety [Ex i] and are installed in safe areas. Their mission is to limit the level of energy that may appear in an electric circuit routed through a potentially explosive area, whatever the connection established upstream of the barrier.

A barrier is made up of:

- resistors that limit the current

- Zener diodes that limit the voltage

- fuses that protect the components

When a fault voltage is applied across the input terminals of the barrier, the voltage that may appear in the explosive zone is limited by a Zener diode, which is in turn protected by a fuse.

The current is limited to an acceptable value by the resistor.

They can be installed in zone 2, thanks to the Ex nA certification in an IP 54 housing.

Zener barrier for analogic signals

Polyester enclosure / DIN Rail mounting

For floating potential wiring

3/4: U0=28V I0=83.97mA P0=587.79mW

2/3: Ua=26.8V Ifm=50mA RL=311.3ohm

Number of channels: 1

Screw terminals

Option: Without

ATEX / IECEx informations:

INERIS 11ATEX0024X / IECEx INE11.0009X

Group II (surface) - category (1) G/D

II(1) GD [Ex ia Ga] IIC, IIB or [Ex iaD Da] IIIC

II3(1) G Ex nA [ia Ga] IIC T4 Gc

Installation in safe zone or zone 2

For equipment installed in zone 0,1,2,20,21,22

See leaflet for a safe use