- RS Stock No.:
- 614-9347
- Mfr. Part No.:
- 84870700
- Manufacturer:
- Crouzet
3 In Global stock for delivery. NCR Plus within 10 working day(s), rest of PH within 14 working days
70 In Global stock for delivery. NCR Plus within 10 working day(s), rest of PH within 14 working days
Added
Price Each
PHP6,608.20
(exc. VAT)
PHP7,401.18
(inc. VAT)
Units | Per Unit |
1 + | PHP6,608.20 |
- RS Stock No.:
- 614-9347
- Mfr. Part No.:
- 84870700
- Manufacturer:
- Crouzet
Technical data sheets
Legislation and Compliance
Product Details
Level Control Relay - HNM
For controlling the filling or emptying level of conductive liquids
0.1 to 5 sec adjustable time delay (anti-wave effect)
Universal model for 24 to 240V AC/DC
Power supply voltage 20.4 to 264Vac/dc
Regulation of maximum and minimum levels using three probes (max 100Mtrs)
Monitoring filling (UP) or emptying (DOWN), selected by a switch on the front panel
Sensitivity adjustable in 3 ranges:- 250Ω → 5KΩ, 5Kohm → 100KΩ, 100KΩ → 1MΩ.
Operating temperature -20 → +50°C
DIN rail mounting
Suitable electrode see stock no. 354-290
Dimensions (mm): H 90, W 35.6, D69
0.1 to 5 sec adjustable time delay (anti-wave effect)
Universal model for 24 to 240V AC/DC
Power supply voltage 20.4 to 264Vac/dc
Regulation of maximum and minimum levels using three probes (max 100Mtrs)
Monitoring filling (UP) or emptying (DOWN), selected by a switch on the front panel
Sensitivity adjustable in 3 ranges:- 250Ω → 5KΩ, 5Kohm → 100KΩ, 100KΩ → 1MΩ.
Operating temperature -20 → +50°C
DIN rail mounting
Suitable electrode see stock no. 354-290
Dimensions (mm): H 90, W 35.6, D69
Note
This is the first conductivity unit to have a DC power option.
Approvals
UL, CSA, GL, GOST, WEEE, RoHS, CE
Liquid Level Relays are used to monitor the levels of conductive liquids, and are available in Up/Down, Minimum, Maximum, and Fill/Empty variations. Liquid Level Relays are straightforward to install and safe to use.
Application Examples
Liquid Level Relays (Conductive Level Sensors) are used in a wide variety of applications including waste water management and the monitoring and management of corrosive liquid media, and designed specifically to provide for the:
Monitoring and control of liquid levels
Protection of pumps against dry running
Ability to detect liquid leaks in a system
Control of media mixing ratios
Control of liquid levels
Protection of pumps against dry running
Ability to detect liquid leaks in a system
Control of media mixing ratios
Control of liquid levels
Specifications
Attribute | Value |
---|---|
Monitoring Application | Level |
Voltage Sensing Range | 24 → 240V ac |
Contact Configuration | DPDT |
Mounting Type | DIN Rail |
Minimum Current Sensed | 10mA |
Maximum Current Sensed | 5A |
Time Delay | 0.1 → 5s |
Frequency Sensing Range | 50 → 60Hz |
Series | HNM |
Operating Temperature Range | +50°C |
Length | 69mm |
Height | 92.6mm |
Current Range | 10 mA → 5A |
Dimensions | 69 x 35 x 92.6mm |
Maximum Operating Temperature | +50°C |
Width | 35mm |
Minimum Operating Temperature | -20°C |