Pepperl + Fuchs 2 Channel Zener Barrier, ATEX

This image is representative of the product range

Subtotal (1 unit)*

PHP11,942.70

(exc. VAT)

PHP13,375.82

(inc. VAT)

Add to Basket
Select or type quantity
Temporarily out of stock
  • 20 unit(s) shipping from June 22, 2026
  • Plus 22 unit(s) shipping from July 13, 2026
  • Plus 26 unit(s) shipping from July 20, 2026
Need more? Click ‘Check delivery dates’ to find extra stock and lead times.
Units
Per Unit
1 +PHP11,942.70

*price indicative

RS Stock No.:
793-4281
Mfr. Part No.:
Z764
Manufacturer:
Pepperl + Fuchs
Find similar products by selecting one or more attributes.
Select all

Brand

Pepperl + Fuchs

Product Type

Zener Barrier

Number of Channels

2

Barrier Type

Zener Barrier

Mount Type

DIN Rail

Hazardous Area Certification

ATEX

Terminal Type

Screw

Safety Current Resistance

1033Ω

IP Rating

IP20

Maximum Safety Current

12mA

Minimum Operating Temperature

-20°C

Maximum Safety Voltage

250V

Maximum Operating Temperature

60°C

Standards/Approvals

TUV, IEC, EN, CE

Series

Z764

RoHS Status: Exempt

COO (Country of Origin):
ID

P&F Dual Channel Zener Diode Barriers


Using a dual channel barrier impedes a direct grounding of the intrinsically safe circuit. The ground is only made in the event of a failure, if the zener diodes conduct. This circuit also suppresses influences of external circuits.

Typical application - thermocouples

Isolation Barriers


Pepperl+Fuchs shunt zener diode barriers are for use as safety interfaces between intrinsically safe and non-intrinsically safe circuits. They are manufactured from Makrolon® and designed to conduct electrical signals - in either direction - between safe and hazardous areas and to limit the amount of energy which can be transferred from a safe to a hazardous area in the event of fault conditions occurring in the safe area. All systems shown are licensed for [EEx ia] IIC Class 1, Div1, Groups A-G

Group and Category

[EEx ia] IIC Class 1, Div1, Groups A-G

Certificate No.

BAS 01 ATEX 7005