Pepperl + Fuchs 2 Channel Zener Barrier, ATEX

Subtotal (1 unit)*

PHP11,942.70

(exc. VAT)

PHP13,375.82

(inc. VAT)

Add to Basket
Select or type quantity
In Stock
  • 24 unit(s) ready to ship from another location
  • Plus 9 unit(s) shipping from May 18, 2026
  • Plus 6 unit(s) shipping from June 15, 2026
Need more? Click ‘Check delivery dates’ to find extra stock and lead times.
Units
Per Unit
1 +PHP11,942.70

*price indicative

RS Stock No.:
793-4272
Mfr. Part No.:
Z757
Manufacturer:
Pepperl + Fuchs
Find similar products by selecting one or more attributes.
Select all

Brand

Pepperl + Fuchs

Number of Channels

2

Product Type

Zener Barrier

Barrier Type

Zener Barrier

Mount Type

DIN Rail

Hazardous Area Certification

ATEX

Terminal Type

Screw

Safety Current Resistance

15.5Ω

IP Rating

IP20

Maximum Safety Current

729mA

Minimum Operating Temperature

-20°C

Maximum Safety Voltage

250V ac

Maximum Operating Temperature

60°C

Standards/Approvals

EN, IEC, TUV, CE

Series

Z757

RoHS Status: Exempt

P&F Dual Channel Zener Diode Barriers


Using a dual channel barrier impedes a direct grounding of the intrinsically safe circuit. The ground is only made in the event of a failure, if the zener diodes conduct. This circuit also suppresses influences of external circuits.

Typical application - thermocouples

Isolation Barriers


Pepperl+Fuchs shunt zener diode barriers are for use as safety interfaces between intrinsically safe and non-intrinsically safe circuits. They are manufactured from Makrolon® and designed to conduct electrical signals - in either direction - between safe and hazardous areas and to limit the amount of energy which can be transferred from a safe to a hazardous area in the event of fault conditions occurring in the safe area. All systems shown are licensed for [EEx ia] IIC Class 1, Div1, Groups A-G

Group and Category

[EEx ia] IIC Class 1, Div1, Groups A-G

Certificate No.

BAS 01 ATEX 7005