Wieland SNO 1012, 24V ac/dc Safety Relay, 2 Safety Contacts
- RS Stock No.:
- 780-5095
- Mfr. Part No.:
- R1.188.3740.0
- Manufacturer:
- Wieland
Subtotal (1 unit)*
PHP9,991.65
(exc. VAT)
PHP11,190.65
(inc. VAT)
Stock information currently inaccessible - Please check back later
Units | Per Unit |
|---|---|
| 1 + | PHP9,991.65 |
*price indicative
- RS Stock No.:
- 780-5095
- Mfr. Part No.:
- R1.188.3740.0
- Manufacturer:
- Wieland
Specifications
Technical data sheets
Legislation and Compliance
Product Details
Find similar products by selecting one or more attributes.
Select all | Attribute | Value |
|---|---|---|
| Brand | Wieland | |
| Product Type | Safety Relay | |
| Safety Contacts | 2 | |
| Contact Configuration | NOC | |
| Reset Method | Manual | |
| Mount Type | DIN Rail | |
| Power Consumption | 1W | |
| Series | SNO 1012 | |
| Terminal Type | Screw | |
| IP Rating | IP40 | |
| Contact Current | 6A | |
| Switching AC Voltage | 240V ac | |
| Minimum Operating Temperature | -25°C | |
| Switching DC Voltage | 50V dc | |
| Standards/Approvals | EN 62061, EN ISO 13849-1 | |
| Maximum Operating Temperature | 55°C | |
| Height | 91.5mm | |
| Width | 22.5mm | |
| Length | 96.5mm | |
| Safety Category | 3 | |
| Hazardous Area Certification | No | |
| Coil Voltage | 24V ac/dc | |
| Select all | ||
|---|---|---|
Brand Wieland | ||
Product Type Safety Relay | ||
Safety Contacts 2 | ||
Contact Configuration NOC | ||
Reset Method Manual | ||
Mount Type DIN Rail | ||
Power Consumption 1W | ||
Series SNO 1012 | ||
Terminal Type Screw | ||
IP Rating IP40 | ||
Contact Current 6A | ||
Switching AC Voltage 240V ac | ||
Minimum Operating Temperature -25°C | ||
Switching DC Voltage 50V dc | ||
Standards/Approvals EN 62061, EN ISO 13849-1 | ||
Maximum Operating Temperature 55°C | ||
Height 91.5mm | ||
Width 22.5mm | ||
Length 96.5mm | ||
Safety Category 3 | ||
Hazardous Area Certification No | ||
Coil Voltage 24V ac/dc | ||
Wieland SNO 1012K Safety Relay
SNO 1012K Safety Relay Function - after the operating voltage (L+/L1) is applied via an unactuated emergency stop button or safety gate contact on A1 and A2, the device can be switched on via a Y1/Y2-connected reset button. When the device is on, the internal relays K1 and K2 are energized and the enabling current paths 13/14 and 23/24 are closed. When the emergency stop button or the safety gate contact is actuated, the current supply of the internal relays is interrupted and the enabling current paths are opened.
Monitoring of E-Stop and Safety Gate applications
Stop Category 0 according to EN 60204-1
Single-channel control
Manual or automatic start
2 enabling current paths
Check of external contactors (EDM)
Compact design
Up to PL d / Category 2 (EN ISO 13849-1)
Up to SILCL 2 (EN 62061)