RS Better World

Eaton Inverter Drive, 3 kW, 3 Phase, DG1 Series 400V ac 9 A

Subtotal (1 unit)*

PHP96,437.15

(exc. VAT)

PHP108,009.61

(inc. VAT)

Add to Basket
Select or type quantity
Stocked by manufacturer
  • Ready to ship from December 29, 2026
Need more? Click ‘Check delivery dates’ to find extra stock and lead times.
Units
Per Unit
1 +PHP96,437.15

*price indicative

Our Better World range features products that make it easy for you to make a greener product choice you can trust.

Learn more about RS Better World products

RS Stock No.:
122-4323
Mfr. Part No.:
9702-1001-00P DG1-347D6FB-C21C
Manufacturer:
Eaton
Find similar products by selecting one or more attributes.
Select all

Brand

Eaton

Product Type

Inverter Drive

Power Rating

3kW

Number of Phases

3

Maximum Output Current

9A

Current Rating

7.6A

Series

DG1

Mount Type

Vertical

IP Rating

IP21

Overall Length

200.9mm

Output Frequency

400Hz

Minimum Supply Voltage

400V ac

Maximum Supply Voltage

400V ac

Minimum Operating Temperature

-10°C

Drive Type

Variable Frequency

Maximum Operating Temperature

+60°C

Standards/Approvals

UL, RoHS, RCM, Ukr SEPRO, cUL, EAC, CE, ISO 9001

Overall Width

153mm

Better World Product

Yes

Better World Claim

Saves Energy

Overall Depth

200.9mm

COO (Country of Origin):
CN

Eaton Inverter Drive, 3kW Power, 400Hz Output Frequency - 9702-1001-00P DG1-347D6FB-C21C


This inverter drive converts three-phase supply into a controlled variable output for industrial motor control. It accepts 380 to 500V supply voltage and supports speed and torque regulation modes suited to pump, fan and general-purpose motor duties while operating in ambient temperatures from -10°C to 50°C.

Features and Benefits:


• 9A maximum output current improves drive capacity for higher load demands
• 7.6A current rating enables defined thermal and duty planning
• 400Hz output frequency supports high-speed motor applications
• IP21 industrial enclosure permits indoor non-condensing installations
• 98.1% efficiency reduces energy losses during continuous operation

Applications


• Suitable for pump and fan speed regulation in HVAC systems
• Ideal for process machinery requiring sensorless Vector control
• Used with screened motor feeders for reduced interference
• Can be used for branch-circuit integration in control panels
• Suitable for needing four-quadrant operation

What communication options are available for integration?


Built-in Modbus RTU and Modbus TCP are provided with optional CANopen, DeviceNet, PROFIBUS and EtherNet/IP support.

How is braking managed for deceleration or high-inertia loads?


An internal brake chopper is fitted with a 63Ω braking resistor specification and an 850VDC switch-on threshold for the braking transistor.

What overload performance can I expect for intermittent demands?


Rated operational current at 150% overload is 7.6A and overload currents reach 11.4A at 150%.

What safety and environmental certifications does it carry?


It holds UL, cUL, CE, RoHS, EAC and UkrSEPRO approvals and meets IEC/EN safety standards.

How should altitude affect installation derating?


Above 1,000 m apply 1% derating per 100 m as specified for elevated installations.

Note

Eaton formerly known as Moeller

Related links