ABB, T16-10 Thermal Overload Relay 1 NO/1 NC, 10A, 7.6 A F.L.C, 10A Contact Rating, 2 W, 600V dc 3
- RS Stock No.:
- 231-8974
- Mfr. Part No.:
- 1SAZ711201R1043 T16-10
- Manufacturer:
- ABB
Subtotal (1 box of 1 unit)*
PHP4,358.75
(exc. VAT)
PHP4,881.80
(inc. VAT)
FREE delivery for orders over ₱3,000.00
In Stock
- 38 unit(s) ready to ship from another location
Need more? Click ‘Check delivery dates’ to find extra stock and lead times.
Box(es) | Per Box |
|---|---|
| 1 + | PHP4,358.75 |
*price indicative
- RS Stock No.:
- 231-8974
- Mfr. Part No.:
- 1SAZ711201R1043 T16-10
- Manufacturer:
- ABB
Specifications
Technical data sheets
Legislation and Compliance
Product Details
Find similar products by selecting one or more attributes.
Select all | Attribute | Value |
|---|---|---|
| Brand | ABB | |
| Product Type | Thermal Overload Relay | |
| FLC Motor Rating | 10, 7.6A | |
| Relay Contact Current | 10A | |
| Series | T16-10 | |
| Power Rating | 2W | |
| Pole and Throw Configuration | 3 | |
| Terminal Type | Screw | |
| Normal State Configuration | 1 NO/1 NC | |
| IP Rating | IP20 | |
| Reset Method | Automatic & Manual | |
| Adjustable Current Range | 7.6 to 10 A | |
| Minimum Operating Temperature | -25°C | |
| Number of Auxiliary Contacts | 2 | |
| Width | 45mm | |
| Maximum Operating Temperature | 60°C | |
| Length | 53.5mm | |
| Contact Voltage | 600V dc | |
| Standards/Approvals | IEC/EN 60947-1, IEC/EN 60947-4-1, IEC/EN 60947-5-1, UL 60947-1, UL 60947-4-1 | |
| Depth | 53.5mm | |
| Control Voltage | 600V dc | |
| Supply Voltage | 690V | |
| Select all | ||
|---|---|---|
Brand ABB | ||
Product Type Thermal Overload Relay | ||
FLC Motor Rating 10, 7.6A | ||
Relay Contact Current 10A | ||
Series T16-10 | ||
Power Rating 2W | ||
Pole and Throw Configuration 3 | ||
Terminal Type Screw | ||
Normal State Configuration 1 NO/1 NC | ||
IP Rating IP20 | ||
Reset Method Automatic & Manual | ||
Adjustable Current Range 7.6 to 10 A | ||
Minimum Operating Temperature -25°C | ||
Number of Auxiliary Contacts 2 | ||
Width 45mm | ||
Maximum Operating Temperature 60°C | ||
Length 53.5mm | ||
Contact Voltage 600V dc | ||
Standards/Approvals IEC/EN 60947-1, IEC/EN 60947-4-1, IEC/EN 60947-5-1, UL 60947-1, UL 60947-4-1 | ||
Depth 53.5mm | ||
Control Voltage 600V dc | ||
Supply Voltage 690V | ||
- COO (Country of Origin):
- DE
ABB T16-10 Series Thermal Overload Relay, 7.6 to 10A FLC Motor Rating, 10A Contact Current Rating - 1SAZ711201R1043 T16-10
This thermal overload relay is an electromechanical device designed for effective motor protection in industrial applications. It operates within a current rating of 7.6 to 10 A and features a compact design with dimensions of 45mm width, 53.5mm depth, and 53.5mm length. The relay is suitable for use in environments where reliable protection against overload and phase failure is critical.
Features & Benefits
• Automatic or manual reset options for flexibility in operation
• Trip class 10 ensures timely response to overload conditions
• Equipped with 1 NC and 1 NO auxiliary contacts for enhanced functionality
• High voltage operational capability up to 690V for versatility
• Designed to connect directly to mini or block contactors, simplifying installation
• Compact design promotes effective space management in control panels
Applications
• Utilised for motor protection in automated systems
• Applied in industrial machinery to prevent phase loss damage
• Suitable for integration with mini contactors for compact solutions
• Used in environments with varying temperature conditions up to +60°C
What is the temperature range for safe operation?
The device operates effectively within a temperature range of -25°C to +60°C, allowing for use in diverse industrial environments.
What types of connections are compatible with this relay?
It features screw terminal connections, accommodating various conductor sizes for flexible installation options.
How does the trip mechanism function during overload situations?
The relay's trip class 10 mechanism offers reliable activation, providing a prompt response to overload conditions to prevent motor damage.
What design considerations ensure this relay is reliable in industrial settings?
The robust construction, high voltage rating, and effective temperature compensation features enhance its reliability in demanding environments.
What is the impact of the auxiliary contacts in operation?
The auxiliary contacts offer additional signals for system monitoring, enhancing supervision and control in motor applications.
Related links
- ABB 3.1 to 4.2 A F.L.C 2 W, 600V dc 3
- ABB Thermal Overload Relay 1 NO/1 NC 16 A Contact Rating, 600V dc 3
- ABB Thermal Overload Relay 1 NO/1 NC 5.7 A Contact Rating, 600V dc 3
- ABB Thermal Overload Relay 1 NO/1 NC 13 A Contact Rating, 600V dc 3
- ABB Thermal Overload Relay 1 NO/1 NC 230 mA Contact Rating, 600V dc 3
- ABB Thermal Overload Relay 1 NO/1 NC 1.7 A Contact Rating, 600V dc 3
- ABB Thermal Overload Relay 1 NO/1 NC 1 A Contact Rating, 600V dc 3
- ABB Thermal Overload Relay 1 NO/1 NC 130 mA Contact Rating, 600V dc 3