Helmholz GmbH & Co. KG Input Module AEA300 Analogue 30V
- RS Stock No.:
- 228-079
- Mfr. Part No.:
- 700-331-4MA20
- Manufacturer:
- Helmholz GmbH & Co. KG
Subtotal (1 unit)*
PHP37,154.70
(exc. VAT)
PHP41,613.26
(inc. VAT)
FREE delivery for orders over ₱3,000.00
In Stock
- 2 unit(s) ready to ship from another location
Need more? Click ‘Check delivery dates’ to find extra stock and lead times.
Units | Per Unit |
|---|---|
| 1 + | PHP37,154.70 |
*price indicative
- RS Stock No.:
- 228-079
- Mfr. Part No.:
- 700-331-4MA20
- Manufacturer:
- Helmholz GmbH & Co. KG
Specifications
Technical data sheets
Legislation and Compliance
Product Details
Find similar products by selecting one or more attributes.
Select all | Attribute | Value |
|---|---|---|
| Brand | Helmholz GmbH & Co. KG | |
| Product Type | Input Module | |
| Input Type | Analogue | |
| Mount Type | DIN Rail | |
| Maximum Supply Voltage | 30V | |
| Number of I/Os | 8 | |
| Maximum Operating Temperature | 60°C | |
| Length | 125mm | |
| Series | AEA300 | |
| Depth | 120mm | |
| Standards/Approvals | EN 60204/IEC 204, VDE 0100/IEC 364, IP20 | |
| Width | 40 mm | |
| Select all | ||
|---|---|---|
Brand Helmholz GmbH & Co. KG | ||
Product Type Input Module | ||
Input Type Analogue | ||
Mount Type DIN Rail | ||
Maximum Supply Voltage 30V | ||
Number of I/Os 8 | ||
Maximum Operating Temperature 60°C | ||
Length 125mm | ||
Series AEA300 | ||
Depth 120mm | ||
Standards/Approvals EN 60204/IEC 204, VDE 0100/IEC 364, IP20 | ||
Width 40 mm | ||
- COO (Country of Origin):
- DE
The Helmholz GmbH & Co. KG Analog input module are set with the STEP 7® software. The module does not have a measuring range module, measuring range switchover operations are performed software-controlled via internal relays. Open circuit monitoring is possible in measuring range 4. to 20mA. If open circuit monitoring is active, the module detects a current <1.185 mA. The wire break is indicated by the group fault LED lighting up. The diagnostic bytes must be evaluated by the user. If the diagnostic alarm is enabled, the module also triggers a diagnostic alarm. If the wire break monitoring is not activated, the module will trigger a diagnostic alarm on reaching underflow.
Isolated from backplane bus
Isolated from power supply
Red LED for group fault display
16 bit DEA 300 front connector
24 V DC via front connector reverse polarity protection
8 inputs for connecting current sensors and current sinks
Related links
- Helmholz GmbH & Co. KG Input Module 700 Analogue 5V
- Helmholz GmbH & Co. KG Input Module 700 Digital 30V
- Helmholz GmbH & Co. KG Ethernet Module 700 30V
- Helmholz GmbH & Co. KG Output Module 700 30V
- Helmholz GmbH & Co. KG I/O Module 700 Digital 30V
- Helmholz GmbH & Co. KG Analogue Output Module 600 Analogue 30V
- Helmholz GmbH & Co. KG Input Module TB20 Digital 24V dc
- Helmholz GmbH & Co. KG Input Module TB20 Digital 230V ac