Seaward PrimeTest 300 AU Portable Appliance Tester, Class I, Class II Test Type

  • RS Stock No. 163-851
  • Mfr. Part No. PT300
  • Manufacturer Seaward
Technical data sheets
Legislation and Compliance
RoHS Status: Not Applicable
COO (Country of Origin): GB
Product Details
Earth Bond Test  
Output Current (Load 2) : ±200mA DC
Test Voltage (o/c): > 4VDC
Test Duration: Programmable within a maximum limit
Measuring Range: 0.01Ω - 19.99Ω
Operating Error: ±5% +2 counts
Measurement Resolution: 0.01Ω
Pass Value: User defined
Insulation Test  
Test Voltages: 500VDC @ 1mA nominal
Test current: >1mA into 500k.; < 2mA into s/c
Test Duration: Programmable within a maximum limit
Measurement Range: 0.10 MΩ - 40MΩ
Operating Error: ±5% +2 digits
Measurement Resolution: 0.01MΩ (Max)
Pass Value: User defined
Differential Leakage  
Test Voltage: 230V +10%, -15%
Maximum Load current: 13Arms
Test Duration: Programmable within a maximum limit
Measurement Range: 0.25 - 19.99mA
Measurement Resolution: 0.01mA
Operating Error: ±5% of rdg +2 digits
Pass Value: User defined
Touch Leakage  
Test Voltage: 230V +10%, -15%
Maximum load current: 13Arms
Test Duration: Programmable within a maximum limit
Measurement Range: 0.10 - 3.50mA
Measurement Resolution: 0.01mA
Operating Error: ±10% of rdg +2 digits
Pass Value: User defined
RCD Test  
Test Voltage: 230V +10 %, -15 %
Test Current: 30mA rms sinusoidal
Test Current Accuracy: +10, -0 %
Test Current Phase: 0°/180° auto switched on alternate cycles
Test Duration: 2000 ms maximum if RCD does not trip
Measuring Range: 10ms - 2000ms
Operating Error: ±10 %
Measurement Resolution: 1ms
Earth Loop Resistance Test  
Test Voltage: 230V +10 %, -15 %
Test Current: Such that it will not trip a 30mA RCD
Measuring Range: 1Ω - 199Ω
Operating Error: ±10 % +2 digits
Measurement Resolution: 0.1Ω (Max)
Lead Test  
Test voltage: 9 VDC
Test Duration: 2s
Test: Live / Neutral Checks for o/c, s/c and crossed
Power Socket Test  
Input voltage range: 230V +10 %, -15 % AC
Indicators: phase to earth voltage phase to neutral voltage neutral to earth
Dimensions 208 x 110 x 60 mm
Weight 1.52 kg
Specifications
Attribute Value
Test Type Class I, Class II
Testing Method Automatic, Manual
Download Yes
Maximum Supply Voltage 230V
Model Number p PrimeTest 300 AU
In Global stock for delivery within 4 - 8 working days
Price Each
PHP 180,301.50
(exc. VAT)
PHP 201,937.68
(inc. VAT)
units
Per Unit
1 +
PHP180,301.50
Related Products
LTDV-suitable for use with EasyPAT, MicroPAT, PAC1500xi, PAT1900xi, ...
Description:
LTDV-suitable for use with EasyPAT, MicroPAT, PAC1500xi, PAT1900xi, PAT2100xi, PAT500H, MPAT40, MPAT60, Megger PAT4, Robin PATs and all Edgcumbe (Metrohm PATs)LTDVR-suitable for use with Seaward PAT2000iee, Seaward PAT 2000, PAT1000s, PAT2000, IT1000, PAT1000x, Supernova, Europa, Europa PAC and Megger PATs ...
PAT450 additional features:. Electrical equipment safety testing in ...
Description:
PAT450 additional features:. Electrical equipment safety testing in accordance with DIN VDE 0701-0702Fully configurable for fast testing and high productivity250V and 500V insulation tests and 200mA continuity testDifferential, substitute or touch leakage current tests with 10 μA resolutionLarge 5.7in. VGA ...
PAT410 Features:. Large 5.7in. VGA backlit colour screen ...
Description:
PAT410 Features:. Large 5.7in. VGA backlit colour screen for clear & easily understandable results5 user defined soft-keys for direct access to frequently used functions Full QWERTY keypad for easy and precise data entry. 10,000 record memory for interruption-free testing.USB port ...
Portable desktop appliance testers providing manual or automatic ...
Description:
Portable desktop appliance testers providing manual or automatic electrical equipment safety testing in accordance with DIN VDE 0701-0702. 250V and 500V insulation tests & 200mA continuity testDifferential, substitute & touch current tests with 10 μA resolutionHigh resolution backlit colour screen ...