- RS Stock No.:
- 492-1529
- Mfr. Part No.:
- 278481 PKZM01-2,5
- Manufacturer:
- Eaton
2 In Global stock for delivery. NCR Plus within 10 working day(s), rest of PH within 14 working days
17 In Global stock for delivery. NCR Plus within 10 working day(s), rest of PH within 14 working days
Added
Price Each
PHP5,433.24
(exc. VAT)
PHP6,085.23
(inc. VAT)
Units | Per Unit |
1 + | PHP5,433.24 |
- RS Stock No.:
- 492-1529
- Mfr. Part No.:
- 278481 PKZM01-2,5
- Manufacturer:
- Eaton
Legislation and Compliance
- COO (Country of Origin):
- DE
Product Details
Eaton Motor Protection Circuit Breaker, 690V AC Supply Voltage, 93 (L) x 90.5 (D) x 45mm (W) - PKZM 01 Series - 278481 PKZM01-2,5
Give your motors a break from dangerous electric current by using this MPCB from Eaton. It keeps a close watch on your circuits and cuts off the power if it senses faults like current overload or short circuits. If your motor works with a three-phase electrical system, you can trust this three-pole device to keep it safe as it's also sensitive to phase imbalance and phase loss. Get the MPCB started by simply pressing the built-in push button. You can use this unit to protect your HVAC systems.
Eaton PKZM01-2,5 MPCB
• Finger and back-of-hand proof to prevent electric shocks
• Compact dimensions of 93 (L) x 45 (W) x 90.5mm (D) for space-saving mounting
• Broad operating temperature range between -25°C and +55°C to withstand harsh industrial environments
• Shock resistant to prevent false tripping in vibrating conditions
• Overload protection range between 1.6 and 2.5A for versatility
• Compact dimensions of 93 (L) x 45 (W) x 90.5mm (D) for space-saving mounting
• Broad operating temperature range between -25°C and +55°C to withstand harsh industrial environments
• Shock resistant to prevent false tripping in vibrating conditions
• Overload protection range between 1.6 and 2.5A for versatility
What's meant by phase imbalance and phase loss?
Phase imbalance is when the current flowing through all three conductors in a three-phase system is uneven, which may damage the motor. A phase loss is when power is suddenly cut off from one of the conductors, causing the other two to overheat.
Note
Eaton formerly known as Moeller
Specifications
Attribute | Value |
---|---|
Current Rating | 1.6 → 2.5 A |
Motor Protection Component | Circuit Breaker |
Supply Voltage | 690 V ac |
Series | Eaton Moeller |
Sensing Type | Current |
Overall Length | 93mm |
Overall Width | 45mm |
Overall Depth | 90.5mm |
Minimum Operating Temperature | -25°C |
Voltage Rating | 690 V ac |
Maximum Operating Temperature | +55°C |
Number of Poles | 3P |
Terminal Type | Screw |
Breaking Capacity | 60 kA |
Horse Power Rating | 1.5HP |